L5: Fault Reset - YASKAWA V1000 Series Installation & Start-Up Manual

Compact vector control drive
Hide thumbs Also See for V1000 Series:
Table of Contents

Advertisement

No.
Name
Number of Auto
L5-01
Restart Attempts
Auto Restart
L5-02
Operation Selection
Fault Reset Interval
L5-04
Time
Fault Reset Operation
L5-05
Selection
YASKAWA ELECTRIC TOEP C710606 09B YASKAWA AC Drive V1000 Installation & Start-Up Manual
Description

L5: Fault Reset

Use L5 parameters to configure Automatic Restart after fault.
Sets the counter for the number of times the
drive attempts to restart when the following
faults occur: GF, LF, OC, OV, PF, PUF, RH,
RR, OL1, OL2, OL3, OL4, UV1. If the drive
faults after an auto restart attempt, the counter
is incremented.
When the drive operates without fault for 10
minutes, the counter will be reset.
Sets fault contact activation during automatic
restart attempts.
0: Fault output (H2-oo = E) not active.
1: Fault output (H2-oo = E) active during
restart attempt.
Sets the amount of time to wait between
performing fault restarts. Enabled when L5-05
is set to 1.
Selects the method of incrementing the restart
counter.
0: Continuously attempt to restart and
increment counter after successful restart (like
Varispeed VS616-F7/G7)
1: Attempt to restart with the interval time set
in L5-04. Every trial increments the counter.
(like Varispeed VS606-V7)
B.2 Parameter Table
Control
Mode
Range Def.
Addr.
O
V/
P
Hex
L
f
M
V
0 to 10
0
A A A 49E
0,1
0
A A A 49F
0.5 to
10.0
A A A 46C
600.0 s
s
0 to 1
0
A A A 467
Pg.
B
355