B.2 Parameter Table
No.
Name
Motor Acceleration
L3-24
Time for Inertia
Calculations
L3-25 Load Inertia Ratio
Speed Agreement
L4-01
Detection Level
Speed Agreement
L4-02
Detection Width
Speed Agreement
L4-03
Detection Level (+/-)
Speed Agreement
L4-04
Detection Width (+/-)
Frequency Reference
L4-05
Loss Detection
Selection
Frequency Reference
L4-06
at Reference Loss
Frequency Detection
L4-07
Conditions
354
Sets the time needed to accelerate the
uncoupled motor at rated torque from stop to
the maximum frequency.
Setting the drive capacity to parameter o2-04
or changing E2-11 will automatically set this
parameter for a 4-pole motor.
Sets the ratio between the motor and machine
inertia.
L4: Frequency Detection
Use L4 parameters to configure frequency detection operation.
These parameters configure the multi-function
output (H2-
Fout Agree 1", "Fref/Set Agree 1", "Frequency
Detection 1," and "Frequency detection 2".
Parameter L4-01 sets the level while parameter
L4-02 sets the hysteresis for the Speed
Detection Output Function.
These parameters configure the Multi-Function
Output (H2-
"Fref/Fout Agree 2", "Fref/Set Agree 2",
"Frequency Detection 3," or "Frequency
Detection 4".
Parameter L4-03 sets the level while parameter
L4-04 sets the hysteresis for the Speed
Detection Output Function.
Sets operation when the frequency reference is
lost (reference drops 90% or more of within
400 ms).
0: Stop - Drive will stop.
1: Run at L4-06 PrevRef - Drive will run at the
percentage set in L4-06 of the frequency
reference before loss.
Sets the frequency reference when a reference
loss was detected and L4-05 = 1. Reference
will be: Fref = Fref at time of loss L4-06.
0: No detection during baseblock.
1: Detection always enabled.
YASKAWA ELECTRIC TOEP C710606 09B YASKAWA AC Drive V1000 Installation & Start-Up Manual
Description
= 2, 3, 4, 5) settings "Fref/
= 13, 14, 15, 16) settings
Control
Mode
Range Def.
O
V/
P
L
f
M
V
0.001 to
A A A 46E
<57>
10.000
0.0 to
1.0 A A A 46F
1000.0
0.0 to
0.0
A A A 499
400.0
Hz
0.0 to
2.0
A A A 49A
20.0
Hz
-400.0
0.0
to
A A A 49B
Hz
+400.0
0.0 to
2.0
A A A 49C
20.0
Hz
0,1
0
A A A 49D
0.0 to
80.0
A A A 4C2
100.0
%
0 to 1
0
A A A 470H —
Addr.
Pg.
Hex