L3: Stall Prevention Function - YASKAWA V1000 Series Installation & Start-Up Manual

Compact vector control drive
Hide thumbs Also See for V1000 Series:
Table of Contents

Advertisement

No.
Name
Stall Prevention
L3-01
Selection during
Acceleration
Stall Prevention Level
L3-02
during Acceleration
Stall Prevention Limit
L3-03
during Acceleration
YASKAWA ELECTRIC TOEP C710606 09B YASKAWA AC Drive V1000 Installation & Start-Up Manual
Description

L3: Stall Prevention Function

Use L3 parameters to configure the stall prevention function.
Selects the stall prevention method used to
prevent excessive current during acceleration.
0: Disabled - Motor accelerates at active
acceleration rate. The motor may stall if load is
too heavy or accel time is too short.
1: General Purpose - When output current
exceeds L3-02 level, acceleration stops.
Acceleration will continue when the output
current level falls below the L3-02 level.
2: Intelligent - The active acceleration rate is
ignored. Acceleration is completed in the
shortest amount of time without exceeding the
current value set in L3-02.
Used when L3-01 = 1 or 2.
100% is equal to the drive rated current.
Decrease the set value if stalling or excessive
current occurs with default setting.
Sets stall prevention lower limit during
acceleration when operating in the constant
power range. Set as a percentage of the drive's
rated current.
B.2 Parameter Table
Control
Mode
Range Def.
Addr.
O
V/
P
Hex
L
f
M
V
0 to 2
1
A A A 48F
<29>
0 to 150
A A A 490
<7>
0 to 100 50% A A A 491
Pg.
B
351