V/F Pattern Selection: E1-03; Setting Instructions For Setting A V/F Pattern; Selecting A Preset V/F Pattern - YASKAWA V1000 Series Installation & Start-Up Manual

Compact vector control drive
Hide thumbs Also See for V1000 Series:
Table of Contents

Advertisement

Note: This data is for an internal dynamic braking resistor of 0.1 to 18.5 kW. For larger units, see
"Dynamic Braking Resistor Unit for VARISPEED-600 Series, TOBPC72060000"

V/f Pattern Selection: E1-03

Parameter E1-03 is only available when using V/f Control. It allows the user to set the
required V/f pattern and drive output voltage. When running a high-speed or special-purpose
motor, this function fine tunes the amount of torque required for the load. Select the V/f
pattern from 15 fixed V/f patterns or 1 user-programmable V/f pattern.
No.
Parameter Name
E1-03
V/f Pattern Selection

Setting Instructions for Setting a V/f Pattern

1.
Set the input voltage for the drive.
page
138.
2.
Select one of the two following V/f patterns:
• *Select one of the 15 preset V/f patterns (setting = 0 through E)
• **Select the Custom V/f pattern (setting = F)
3.
In case of * the following parameters are automatically set.
In case of **, the following parameters are adjustable.
E1-04 (Max Output Frequency), E1-05 (Max Voltage), E1-06 (Base Frequency), E1-
07 (Mid Output Frequency), E1-08 (Mid Output Frequency Voltage), E1-09 (Min
Output Frequency), E1-10 (Min Output Frequency Voltage)
Figure 4.24

Selecting a Preset V/f Pattern

There are two types of V/f patterns: a method to select one of the 15 presets (set value: 0 to
E) and a method to select arbitraty V/f pattern (set value: F). Refer to
YASKAWA ELECTRIC TOEP C710606 09B YASKAWA AC Drive V1000 Installation & Start-Up Manual
4.6 Basic Drive Setup Adjustments
Description
0 to E: Select from 15 preset V/f patterns.
F: Custom V/f pattern (allows use of E1-04 through E1-10).
Refer to Drive Input Voltage Setting: E1-01 on
Output Voltage (V)
E1-05
E1-12
E1-13
E1-08
E1-10
E1-09
E1-07 E1-06 E1-11 E1-04
Frequency (Hz)
Figure 4.24 V/f Pattern
Setting
Default
Range
0 to F
F
Table
4.20.