3.11 Braking Resistor

Dynamic braking (DB) helps bring the motor to a smooth and rapid stop when working with
high inertia loads. As the drive lowers the frequency of a motor with high inertia connected,
regeneration occurs. This can cause an overvoltage situation when the regenerative energy
flows back into the DC bus capacitors. A braking resistor prevents these overvoltage faults.
NOTICE: Do not allow unqualified personnel to use the product. Failure to comply could result in damage to
the drive or braking circuit. Carefully review the braking resistor instruction manual when connecting a
braking option to the drive.
Note: The braking circuit must be sized properly in order to dissipate the power required to decelerate
the load in the desired time. Ensure that the braking circuit can dissipate the energy for the set
deceleration time prior to running the drive.
Use a thermal overload relay or an over-temperature contact to interrupt input power to the
drive in the event the braking resistor overheats.
In the event of a possible thermal overload, the relay will trigger the input contactor and
prevent the braking resistor from burning up.
Installation
WARNING! Fire Hazard. The braking resistor connection terminals are B1 and B2. Do not connect a braking
resistor directly to any other terminals. Improper wiring connections could result in death or serious injury by
fire. Failure to comply may result in damage to the braking circuit or drive.
NOTICE: Connect braking resistors to the drive as shown in the I/O wiring examples. Improperly wiring
braking circuits could result in damage to the drive or equipment.

Installation Procedure

1.
Disconnect all electrical power to the drive and wait at least five minutes before
servicing the drive and any connected components.
2.
Remove drive front cover.
3.
Use a voltmeter to verify that voltage is disconnected from incoming power
terminals and that the DC bus no longer holds a charge.
YASKAWA ELECTRIC TOEP C710606 09B YASKAWA AC Drive V1000 Installation & Start-Up Manual
3.11 Braking Resistor
3
83