3.2 Standard Connection Diagram
Figure 3.1
Terminals +1, +2, , B1, and B2
are for connecting options.
Never connect power supply
lines to these terminals.
For single phase 200 V
power supply, use
R/L1 and S/L2.
R/L1
Three phase
power supply
S/L2
200 to 240 V
T/L3
2 MCCB THRX OFF ON
Thermal relay for
motor cooling fan
MC
MC MA
Digital inputs
(default setting)
Main speed
frequency
reference.
Multi-function
programmable
56
_
2 MCCB
r1
s1
t1
MC
1 MCCB
* 4
Forward run/stop
MC
SA
Reverse run/stop
MC
THRX
External fault
SA
Fault reset
Multi-step
TRX
speed 1
main/aux switch
SA
Multi-step
TRX
speed 2
Fault relay
Jog reference
2 k
Safety switch
Safe Disable
Input
Jumper
Figure 3.1 Drive Standard Connection Diagram
YASKAWA ELECTRIC TOEP C710606 09B YASKAWA AC Drive V1000 Installation & Start-Up Manual
DC reactor
* 1
(option)
Thermal relay
(option)
*3
Jumper
-
+2
+1
B1
V1000
R/L1
Main circuit
S/L2
T/L3
Control circuit
S1
S2
S3
S4
S5
S6
S7
+ 24 V 8 mA
24 V
* 5
Sink
DIP
Source
switch S3
SC
Shield ground
0 V
terminal
Pulse train input
RP
(max. 32 kHz)
Setting power supply
+V
+10.5 max. 20 mA
A1
0 to +10 V (20 k )
A2
0 to +10 V (20 k )
(0)4 to 20 mA (250
)
AC
DIP
switch
S2
HC
* 8
H1
Cable shield ground
shielded line
twisted-pair shielded line
control terminal
main circuit terminal
* 2
Braking resistor
(option)
FU
r1
B2
FV
s1
FW
t1
U
U/T1
V
V/T2
W
W/T3
Ground
10
or less (400 V class)
Option card
100
or less (200 V class)
connector
* 6
DIP switch S1
Digital output
250 Vac, 10 mA to 1 A
V
I
30 Vdc, 10 mA to 1 A
(default setting)
Fault
MA
Digital output
MB
5 ~ 48 Vdc
2 to 50 mA
MC
(default setting)
During Run
P1
(photocoupler 1)
Frequency agree
P2
(photocoupler 2)
Photocoupler
PC
output common
MP
Pulse train output
0 to 32 kHz
Analog monitor
AM
output
+
AM
0 to +10 Vdc
AC
(2 mA)
-
Termination
Comm.
resistor
connector
120
, 1/2 W
R +
R -
S +
S -
IG
Motor
Cooling fan
M
M
* 7
Monitor
output
MEMOBUS/
Modbus comm.
RS-485/422

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents