4.7 Test Run

Operation Instructions

The following example illustrates a procedure to run the drive using the digital operator.
Note: Before starting the motor, set the frequency reference to 6 Hz.
Programming Modes on page 97
1.
Turn on the power to the drive. The initial display appears.
Press the
2.
turn on.
Press
to give the drive a run command. RUN will light
RUN
3.
and the motor will rotate at 6 Hz.
Ensure the motor is rotating in the correct direction and no faults or
4.
alarms occur.
If there is no error in step 4, press
reference. Increase the frequency in 10 Hz increments verifying
smooth operation results at all speeds. For each frequency monitor
5.
the drive output current (U1-03) through the LED operator to
confirm the current is well below the motor rated current. Example:
6 Hz → 50 Hz/60 Hz .
Note:
Refer to Auto-Tuning Errors on page 186
errors that occur while Auto-Tuning the drive.
162
for instructions.
Step
key to select LOCAL. The LO/RE LED will
YASKAWA ELECTRIC TOEP C710606 09B YASKAWA AC Drive V1000 Installation & Start-Up Manual
to increase the frequency
for help with
Refer to The Drive and
Display/Result
STOP
STOP
Off
Motor
On
Forward