5.6 Operator Programming Errors
LED Operator Display
Run command for a 2-wire sequence was set, but forward/
reverse command for a 2-wire sequence was not. "Drive
Enable" is set to a multi-function contact input (H1-01 =
6A or H1-02 = 6A).
• Two of the following functions are set at the same time:
• Up / Down Command (10 vs. 11)
• Up 2 / Down 2 Command (75 vs. 76)
• Hold Accel/Decel Stop (A)
• Analog Frequency Reference Sample / Hold (1E)
• Offset Frequency 1, 2, 3 Calculations (44, 45, 46)
The Up/Down command (10, 11) is enabled at the same
time as PID control (b5-01).
• One of the following settings at the multi-function input
terminals:
• External Search Command 1 and External Search
Command 2 (61 vs. 62)
• Fast-Stop N.O. and Fast-Stop N.C. (15 vs. 17)
• KEB for Momentary Power Loss and High Slip Braking
(65, 66, 7A, 7B vs. 68)
• Motor Switch Command and Accel/Decel Time 2 (16 vs.
1A)
• KEB Command 1 and KEB Command 2 (65, 66 vs. 7A,
7B)
• FWD Run Command (or REV) and FWD/REV Run
Command (2-wire) (40, 41 vs. 42, 43)
• External DB Command and Drive Enable (60 vs. 6A))
• Motor Switch Command and UP2/DOWN2 Command
(16 vs. 75, 76)
• One of the following settings was entered while
H1-
= 2 (Alternative Reference):
• b1-15 = 4 (Pulse Train Input) and H6-01 (Pulse Train
Input Function Selection) not = 0 (Frequency Reference)
• b1-15 or b1-16 set to 3 but no option card connected
• Although b1-15 = 1 (Analog Input) and H3-02 or H3-10
are set to 0 (Frequency Bias).
H2-
= 38 (Drive Enabled) but H1-
6A (Drive Enable).
H1-
= 7E (Direction Detection) although H6-01 is not
set to 3 (Simple V/f with PG).
LED Operator Display
218
is not set to
oPE04
YASKAWA ELECTRIC TOEP C710606 09B YASKAWA AC Drive V1000 Installation & Start-Up Manual
Error Name
Correctly set functions that need to be enabled in
combination with other functions.
• Check if contradictory settings have been assigned to
the multi-function input terminals at the same time.
• Correct setting errors.
Disable control PID (b5-01 = "0") or disable the Up/
Down command.
Check for contradictory settings assigned to the
multi-function input terminals at the same time.
Correct setting errors.
Correct the settings for the multi-function input terminal
parameters.
Error Name
Initialization required.