Pm Motor Parameters - YASKAWA V1000 Series Installation & Start-Up Manual

Compact vector control drive
Hide thumbs Also See for V1000 Series:
Table of Contents

Advertisement

No.
Name
Enter the Yaskawa motor code for the PM
motor being used. Various motor parameters
are automatically set based on the value of
this parameter.
Note: Set to FFFF when using a specialized
or custom motor. For all other motors:
Motor Code
E5-01
Selection (for
<25>
PM motor)
All motor parameters are re-initialized to
factory settings when this parameter is set.
Motor Rated
E5-02
Capacity (for
Sets the rated capacity of the motor.
<25>
PM motor)
Motor Rated
E5-03
Sets the motor rated current in amps.
Current
E5-04
Motor Poles
Sets the number of motor poles.
<25>
E5-05
Motor
Set the resistance for each motor phase in
units of 0.001 Ω.
Resistance
<25>
E5-06
Motor d Axis
Sets the d axis inductance in units of
Inductance
0.01 mH.
<25>
E5-07
Motor q Axis
Sets the q axis inductance in units of
Inductance
0.01 mH.
<25>
YASKAWA ELECTRIC TOEP C710606 09B YASKAWA AC Drive V1000 Installation & Start-Up Manual
Description
E5: PM Motor Parameters
0 0 0 0
Motor voltage
class and
capacity
0: Pico motor
0: 1800 r/min
(SMRA series)
series
1: Derated torque
1: 3600 r/min
IPM motor
series
(SSR1 series)
2: 1750 r/min
2: Constant torque
series
IPM motor
3: 1450 r/min
(SST4 series)
series
4: 1150 r/min
series
F: Custom motor
B.2 Parameter Table
Control
Mode
Range
Def.
O
P
V/f
L
M
V
0000 to
<12> <
FFFF
38>
0.10 to
<10>
18.5
10 to
200% of
drive
<4>
rated
current
<27>
2 to 48
<10>
0.000 to
<10>
65.000
0.00 to
<10>
300.00
0.00 to
<10>
600.00
Addr.
Pg.
Hex
S
329
S
32A
S
32B
B
S
32C
S
32D
S
32E
S
32F
331

Hide quick links:

Advertisement

Table of Contents
loading