Changing Analog Output Settings

The following example illustrates how to program analog output terminal FM to generate a
signal proportional to drive output current (monitor U1-03).

Using H4-01 to Display Monitor Contents

1.
Turn on the power to the drive. The initial display appears.
Press
until the Parameter setting menu is displayed.
2.
3.
Press
to enter the Parameter setting menu.
4.
Press
and
5.
Press
to display the value currently set to H4-01.
Press
and
6.
7.
Save the setting by pressing
8.
The display automatically returns to the parameter setting menu.
YASKAWA ELECTRIC TOEP C710606 09B YASKAWA AC Drive V1000 Installation & Start-Up Manual
4.6 Basic Drive Setup Adjustments
Select the data to output through multi-function analog output terminal AM.
Set the desired monitor parameter to the digits available in U -
example, enter "103" for U1-03.
When using this terminal as a through terminal or when not using it at all,
set "000" or "031".
Sets the voltage level gain of multi-function analog output 1 (terminal AM).
The bias to be added ranges from 0 to +/- 10% when 10 V is assumed to be
100%.
Sets the voltage level bias for terminal AM.
The bias added is 0 to ±10% with a maximum voltage output of
10 V as 100%.
Step
to select H4-01.
to set the output current (103).
.
Description
Display/Result
. For
4
145