Figure 4.32
Three-Phase, 200 Vac
(AC400 V)
Figure 4.33
Setting Procedure
1.
Turn on the power to the drive. The initial display appears.
Set the frequencies listed below to the specified parameters:
1. d1-01 = 5 Hz: Step 1
2.
2. d1-02 = 20 Hz: Step 2
3. d1-03 = 50 Hz: Step 3
4. d1-04 = 60 Hz: Step 4
Press the
key until the initial display appears.
3.
4.
turns on.
YASKAWA ELECTRIC TOEP C710606 09B YASKAWA AC Drive V1000 Installation & Start-Up Manual
SW1
SW2
Figure 4.32 Control Terminals for 4 Multi-Step Speeds
Frequency
Reference
Freq Ref 1
Forward/Reverse Run/Stop
OFF
Multi-Step Speed 1
Multi-Step Speed 2
OFF
Figure 4.33 4-Step Speed Time Chart
Step
<1>
<2>
Drive
U/T1
R/L1
V/T2
S/L2
W/T3
T/L3
S5
S6
SC
Freq Ref 4
Freq Ref 3
Freq Ref 2
ON
ON
ON
ON
4.7 Test Run
M
Display/Result
169