Preparing The Ends Of Shielded Cables; Wiring The Frequency Reference To The Control Circuit Terminals - YASKAWA V1000 Series Installation & Start-Up Manual

Compact vector control drive
Hide thumbs Also See for V1000 Series:
Table of Contents

Advertisement

Figure 3.23
A – Drive side
B – Connect shield to ground terminal
of drive.
C – Insulation
When setting the frequency by analog reference from an external potentiometer, use shielded
twisted-pair wires and ground the shield of twisted-pair wires to the ground terminal of the
drive.
NOTICE: The analog signal lines between the drive and the operator station or peripheral equipment should
not exceed 50 meters when using an analog signal from a remote source to supply the frequency reference.
Failure to comply could result in poor system performance.
Figure 3.24
A – Drive
B – Ground terminal
(shield connection)
C – (RP) Pulse train
(maximum 32 kHz)
D – (+V) Frequency setting power source +10.5 Vdc maximum 20 mA
Figure 3.24 Wiring the Frequency Reference to the Control Circuit Terminals (External Reference)
YASKAWA ELECTRIC TOEP C710606 09B YASKAWA AC Drive V1000 Installation & Start-Up Manual
A
F
B
Figure 3.23 Preparing the Ends of Shielded Cables
RP
+V
2 k
G
A1
A2
AC
3.7 Control Circuit Wiring
D
C
E
D – Control device side
E – Shield sheath
(Insulate with tape)
F – Shield
A
B
C
D
E
F
E – (A1) Main speed frequency
reference
0 to +10 Vdc (20 kΩ)
F – (A2) Multi-function analog input
0 to +10 Vdc (20 kΩ) or
4 to 20 mA (250 Ω)/
0 to 20 mA (250 Ω)
G – Frequency setting potentiometer
3
77