4.6 Basic Drive Setup Adjustments
No.
Parameter Name
E1-04
Maximum Output Frequency (FMAX)
E1-05
Maximum Voltage (VMAX)
E1-06
Base Frequency (FA)
E1-07
Mid Output Frequency (FB)
Note: The default setting for the V/f pattern is for a custom V/f pattern (E1-03 = F).
Setting
0
50 Hz
1 (F)
60 Hz
2
60 Hz (with 50 Hz base)
3
72 Hz (with 60 Hz base)
4
50 Hz, Heavy Duty 3
5
50 Hz, Heavy Duty 2
6
60 Hz, Heavy Duty 3
7
60 Hz, Heavy Duty 2
8
50 Hz, mid starting torque
9
50 Hz, high starting torque
A
60 Hz, mid starting torque
B
60 Hz, high starting torque
C
90 Hz (with 60 Hz base)
D
120 Hz (with 60 Hz base)
E
180 Hz (with 60 Hz base)

V/f Pattern Characteristics

These graphs apply to 200 V class drives; double the values for 400 V class drives.
• Constant Torque Characteristics, Settings 0 through 3
140
Table 4.20 V/f Patterns
Specification
YASKAWA ELECTRIC TOEP C710606 09B YASKAWA AC Drive V1000 Installation & Start-Up Manual
No.
E1-08
Mid Output Frequency Voltage (VC)
E1-09
Minimum Output Frequency (FMIN)
E1-10
Minimum Output Frequency Voltage (VMIN)
Characteristic
For general purpose applications, torque
Constant torque
remains constant regardless of speed
changes.
For applications where torque changes with
Reduced or
the speed like fans, pumps, and others that
variable torque
require reduced torque relative to the load.
• High starting should be selected only when:
• Wiring between the drive and motor exceeds
150 m
High starting
• Large amount of starting torque is required
torque
• AC reactor is installed
• motor exceeds the largest motor
recommended for that drive used
When operating at speeds greater than 60 Hz
Constant output
motor requires constant voltage. Above 60
Hz, motor operates in constant power range.
Parameter Name
Application