5.9 Troubleshooting without Fault Display
Cause
The Stall Prevention level during run has
been set too low.
Although the drive is operating in Open
Loop Vector motor control method,
Auto-Tuning has not been performed.
Drive reached the limitations of the V/f
motor control method.
Drive Frequency Reference Differs from the Controller Frequency
■
Reference Command
Cause
The analog input frequency gain and bias
are set to incorrect values.
A frequency bias signal is being entered
via analog input terminals A1 or A2.
Poor Speed Control Accuracy
■
Cause
Drive reached the slip compensation
limit.
Motor-rated voltage is set too high in
Open Loop Vector Control.
Auto-Tuning did not complete properly
for Open Loop Vector Control.
234
• Check the Stall Prevention level during run (L3-06).
• If L3-06 is set too low, speed will drop as the drive outputs torque.
• Increase the setting value.
• Perform Auto-Tuning.
• Calculate motor data and reset motor parameters.
• Switch to the V/f motor control method (A1-02 = "0").
• The motor cable may be long enough (over 50 m) to require Auto-
Tuning for line-to-line resistance. Also be aware that V/f Control is
comparatively limited when it comes to producing torque at low speeds.
• Consider switching to Open Loop Vector Control.
• Check the frequency reference terminal input gain level assigned to
terminals A1 and A2, as well as the frequency reference input bias to
terminal A1 and A2 (parameters H3-03, H3-04, and H3-12).
• Set these parameters to the appropriate values.
• If multi-function analog input terminals A1 and A2 are set for frequency
reference (H3-02 = 0 and H3-10 = 0), the addition of both signals builds
the frequency reference.
• Ensure that H3-02 and H3-10 are set appropriately.
• Check the input level set for terminals A1 and A2 (U1-13, U1-14).
• Check the slip compensation limit (C3-03).
• Increase the value set to C3-03.
• The input voltage for the drive determines the maximum output voltage.
A drive with an input of 200 Vac can only output a maximum of 200 Vac.
Open Loop Vector Control sometimes calculates an output voltage
reference value that exceeds the maximum drive output voltage level,
resulting in a loss of speed control accuracy.
• Use a motor with a lower voltage rating (a vector control motor).
• Increase the input power voltage.
• Perform Auto-Tuning again.
YASKAWA ELECTRIC TOEP C710606 09B YASKAWA AC Drive V1000 Installation & Start-Up Manual
Possible Solutions
Possible Solutions
Possible Solutions