B.2 Parameter Table
H1-
Function
Setting
3
Multi-Step Speed Reference 1
4
Multi-Step Speed Reference 2
5
Multi-Step Speed Reference 3
6
Jog Reference Selection
7
Accel/Decel Time 1
8
Baseblock Command (N.O.)
9
Baseblock Command (N.C.)
A
Accel/Decel Ramp Hold
B
Drive Overheat Alarm (OH2)
C
Terminal A2 Enable
F
Not used
10
Up Command
11
Down Command
12
Forward Jog
13
Reverse Jog
14
Fault Reset
15
Fast-Stop (N.O.)
16
Motor 2 Selection
17
Fast-stop (N.C.)
18
Timer Input Function
19
PID Disable
338
H1 Multi-Function Digital Input Selections
Used to select Multi-Step Speeds set in d1-01 to d1-16
Open: Selected speed reference
Closed: Jog Frequency reference (d1-17). Jog has
priority over all other reference sources.
Used to switch between Accel/Decel. Time 1/2
Open: Normal operation
Closed: No drive output
Open: No drive output
Closed: Normal operation
Closed: The drive pauses during acceleration or
deceleration and maintains the output frequency.
Closed: Displays an OH2 alarm
Open: Terminal A2 disabled
Closed: Terminal A2 enabled
Select this setting when not using the terminal or when
using the terminal in a pass-through mode.
Open: Maintains the current frequency reference
Closed: Increases or decreases the current frequency
reference. Ensure that the increase and decrease
commands are set in conjunction with one another. The
frequency reference source must be set to operator (b1-
01 = 0).
Closed: Runs forward at the Jog Frequency d1-17.
Closed: Runs reverse at the Jog Frequency d1-17.
Closed: Resets faults if the cause is cleared and the Run
command is removed.
Closed: Decelerates at the Fast-Stop time C1-09.
To restart the Fast-Stop input must be released and Run
must be cycled.
Open: Motor 1 (E1-
Closed: Motor 2 (E3-
Open: Decelerates according to C1-09 (Fast-stop Time)
Set the timer delay using parameters b4-01 and b4-02.
Ensure this function is set in conjunction with the multi-
function output timer (H2-
Closed: PID control disabled
YASKAWA ELECTRIC TOEP C710606 09B YASKAWA AC Drive V1000 Installation & Start-Up Manual
Description
, E2-
)
, E4-
)
= 12).
Control
Mode
Pg.
V/
O
P
f
LV
M
O O O —
O O O —
O O O —
O O O —
O O O —
O O O —
O O O —
O O O —
O O O —
O O O —
O O O —
O O O —
O O O —
O O O —
O O O —
O O O —
O O O —
O O O —
O O O —
O O O —
O O O —