5.6 Operator Programming Errors
LED Operator Display
LED Operator Display
Attempted to use a function in the V/f motor control
method that is only possible in Open Loop Vector Control.
Simple V/f with PG was enabled while not in V/f Control
(H6-01 = 3).
In Open Loop Vector Control, n2-02 is greater than n2-03
In Open Loop Vector Control, C4-02 is greater than C4-06
In PM Open Loop Vector Control, parameters E5-02 to
E5-07 are set to 0.
The following conditions are true in PM Open Loop
Vector Control:
E5-03 does not equal 0
E5-09 and E5-24 are both equal to 0, or neither equals 0
Note: Use U1-18 to find which parameters are set outside the specified setting range.
Other errors are given precedence over OPE08 when multiple errors occur at the same time.
LED Operator Display
The following simultaneous contradictory settings:
b5-15 not 0.0 (PID Sleep Function Operation Level)
The stopping method is set to either DC injection braking
or coast to stop with a timer (b1-03 = 2 or 3).
LED Operator Display
220
oPE08
Cause
oPE09
Cause
oPE10
YASKAWA ELECTRIC TOEP C710606 09B YASKAWA AC Drive V1000 Installation & Start-Up Manual
Error Name
Error Name

Parameter Selection Error

A function has been set that cannot be used in the motor
control method selected.
Possible Solutions
Check the motor control method and the functions
available.
To use Simple V/f with PG, ensure the motor control
method has been set to V/f Control (A1-02 = "0").
Correct parameter settings so that n2-02 is less than
n2-03.
Correct parameter settings so that C4-02 is less than
C4-06.
• Set the correct motor code in accordance with the motor
being used (E5-01).
• When using a special-purpose motor, set E5-
accordance with the Test Report provided.
Set E5-09 or E5-24 to the correct value, and set the other
to "0".
Set the motor-rated current for PM to "0" (E5-03).
Error Name

PID Control Selection Fault

PID control function selection is incorrect.
Requires that PID control is enabled (b5-01 = 1 to 4).
Possible Solutions
• Set b5-15 to another value besides 0.
• Set the stopping method to coast to stop or ramp to stop
(b1-03 = "0" or "1").
Error Name

V/f Data Setting Error

The following setting errors have occurred where:
E1-04 is greater than or equal to E1-06 is greater than or
equal to E1-07 is greater than or equal to E1-09.
Or the following setting errors have occurred:
E3-04 is greater than or equal to E3-06 is greater than or
equal to E3-07 is greater than or equal to E3-09.
in