3330: 3-Wire Initialization

Returns all parameters to factory default values for 3-wire control.

1110: User Initialization

Returns all parameters to backed-up values stored at the time the user set o2-03 = 1 and
pressed enter to back-up parameter settings.
5550: Uploads Parameter Data from the Removable Control Circuit Terminal Board
Replacing either the removable control circuit terminal board or the drive and applying main
power may result in an oPE04 fault. If parameter setting data in the removable control circuit
terminal board is correct, set A1-03 to "5550" to upload the data to the drive.
Note:
Refer to Run Command Input Selection: b1-02 on page
and 3-wire sequence.
Note: Initializing the drive for 2-wire sequence (A1-03 = 2220) returns all drive parameters to factory
settings. Back up all parameters in the event of accidental initialization. the data with 2-wire
sequence returns all the set parameters to the factory settings.
Values: o2-03 on page
Application Presets: A1-06
The drive features application presets to facilitate the set up of commonly used applications
such as a water supply pump, conveyor, exhaust fan, HVAC fan, compressor, hoist, and
crane. Selecting one of these presets automatically sets the required parameters to the
optimum values and changes the appropriate I/O terminal settings for that specific
application.
Refer to Application Presets on page 111
Verify all I/O signals and external sequences before operating the motor.
Application Preset Specifics on page 118
Users are able to make further adjustments to these settings using the Setup Mode.
No.
Parameter Name
A1-06
Appilcaton Presets
<1> All general-purpose parameters are accessible when A1-06 = 0.
YASKAWA ELECTRIC TOEP C710606 09B YASKAWA AC Drive V1000 Installation & Start-Up Manual
4.6 Basic Drive Setup Adjustments
164.
when selecting a hoist application.
0: General-purpose (A2 parameters are not affected)
1: Water supply pump
2: Conveyor
3: Exhaust fan
4: HVAC fan
5: Air compressor
6: Hoist
7: Crane (hoist, traverse)
127, for more information on a 2-wire
Refer to Backing Up Parameter
Setting Range
Refer to Hoist
Default
0
<1>
123
4