Motor Rotates In One Direction Only; Motor Is Too Hot - YASKAWA V1000 Series Installation & Start-Up Manual

Compact vector control drive
Hide thumbs Also See for V1000 Series:
Table of Contents

Advertisement

Cause
The forward direction for the motor is
set-up incorrectly.
The motor is running at almost 0 Hz and
the Speed Search estimated the speed to
be in the opposite direction.
Note: Check the motor specifications for the forward and reverse directions. The motor specifications
will vary depending on the manufacturer of the motor.

Motor Rotates in One Direction Only

Cause
The drive prohibits reverse rotation.
A Reverse run signal has not been
entered, although 3-wire sequence is
selected.

Motor is Too Hot

Cause
The load is too heavy.
The air around the motor is too hot.
The drive is operating in a vector control
mode but Auto-Tuning has not yet been
performed.
YASKAWA ELECTRIC TOEP C710606 09B YASKAWA AC Drive V1000 Installation & Start-Up Manual
5.9 Troubleshooting without Fault Display
Possible Solutions
• Typically, forward is designated as being counterclockwise when
looking from the motor shaft (refer to the figure below).
• 1. Forward Rotating Motor (looking down the motor shaft)
2. Motor Shaft
• Disable bi-directional search (b3-14 = "0") so that Speed Search is
performed only in the specified direction.
Possible Solutions
• Check parameter b1-04.
• Set the drive to allow the motor to rotate in reverse (b1-04 = "0").
• Make sure that one of the input terminals S3 to S7 used for the 3-wire
sequence has been set for reverse.
Possible Solutions
• If the load is too heavy for the motor, the motor will overheat as it
exceeds its rated torque value for an extended period of time.
• Keep in mind that the motor also has a short-term overload rating in
addition to the possible solutions provided below:
• Reduce the load.
• Increase the acceleration and deceleration times.
• Check the values set for the motor protection (L1-01, L1-02) as well as
the motor rated current (E2-01).
• Increase motor capacity.
• Check the ambient temperature.
• Cool the area until it is within the specified temperature range.
• Perform Auto-Tuning.
• Calculate the motor value and reset the motor parameters.
• Change the motor control method to V/f Control (A1-02 = "0").