YASKAWA V1000 Series Installation & Start-Up Manual page 381

Compact vector control drive
Hide thumbs Also See for V1000 Series:
Table of Contents

Advertisement

No.
Name
Run Command
U4-21
Source Selection
MEMOBUS/Modbus
U4-22
Communications
Reference
Option Card
U4-23
Reference
YASKAWA ELECTRIC TOEP C710606 09B YASKAWA AC Drive V1000 Installation & Start-Up Manual
Description
Displays the source for the Run command as
XY-nn.
X: Indicates which Run source is used:
1 = Reference 1 (b1-02)
2 = Reference 2 (b1-16)
Y: Input power supply data
0 = Operator
1 = External terminals
2 = Not used
3 = MEMOBUS/Modbus communications
4 = Option
5 = Not used
6 = CASE
7 = DWEZ
nn: Run command limit status data
00: No limit status.
01: Run command was left on when stopped
in the PRG mode.
02: Run command was left on when
switching from local to remote operation.
03: Waiting for the soft charge bypass
contactor after the power is switched on (UV
or UV1 flashes after 10 seconds).
04: Waiting for "Run Command Prohibited"
time period to end.
05: Fast-stop (digital input (H1-
operator)
06: b1-17 (run command given at power-up).
07: During Baseblock while coast to stop
with timer
08: Frequency reference is below minimal
reference during base block
09: Waiting for Enter command
Displays the drive control data set by
MEMOBUS/Modbus communications
register No. 0001H as a 4 digit hexadecimal
number.
Displays drive control data set by an option
card as a 4 digit hexadecimal number.
B.2 Parameter Table
Analog
Output
Unit
Level
= 15),
Control
Mode
Addr.
O
V/
P
Hex
L
f
M
V
A A A 7DD
B
A A A 7DE
A A A 7DF
381