No.
Name
DWEZ Connection
r1-38
Parameter 19 (lower)
DWEZ Connection
r1-39
Parameter 20 (upper)
DWEZ Connection
r1-40
Parameter 20 (lower)
T: Motor Tuning
Enter data into the following parameters to tune the motor and drive for optimal
performance
No.
Name
Motor
T1-00
Selection 1/2
Auto-Tuning
T1-01
Mode Selection
Motor Rated
T1-02
Power
T1-03
Motor Rated
Voltage
<24>
YASKAWA ELECTRIC TOEP C710606 09B YASKAWA AC Drive V1000 Installation & Start-Up Manual
Description
Parameter 19 for connecting DWEZ (lower).
Parameter 20 for connecting DWEZ (upper).
Parameter 20 for connecting DWEZ (lower).
Description
Selects which set of motor parameters are used and
set during Auto-Tuning. If Motor 2 selection
(H1-
= 16) is not selected, this parameter will
not be displayed.
1: 1st Motor - E1 to E2
2: 2nd Motor - E3 to E4 (this selection is not
displayed if motor 2 has not been selected)
Selects the Auto-Tuning mode.
0: Rotational Auto-Tuning
2: Stationary Auto-Tuning, Terminal resistance
only,
3: Rotational Auto-Tuning for V/f control
(necessary for Energy Savings and Speed
Estimation type speed search)
Sets the motor rated power in kilowatts (kW).
Note: If motor power is given in horsepower,
power in kW can be calculated using the following
formula: kW = HP x 0.746.
Sets the motor rated voltage in volts (V).
B.2 Parameter Table
Control
Mode
Range Def.
Addr.
O
V/
P
L
f
M
V
0000 to
0
A A A 1865 —
FFFF(H)
0000 to
0
A A A 1866 —
FFFF(H)
0000 to
0
A A A 1867 —
FFFF(H)
Control
Mode
Range
Def.
O
V/
P
L
f
M
V
A A −
1, 2
1
2 or 3
in V/f
0 or 2
0, 2, 3
A A −
in OLV
<54>
2 for
Motor
2
0.00 to
0.40
A A −
650.00
kW
0.0 to
200.0
A A −
255.5
V
Pg.
Hex
Addr.
Pg.
Hex
700
B
701
702
703
371