3.6

Main Circuit Wiring

This section describes the functions, specifications, and procedures required to safely and
properly wire the main circuit of the drive.
NOTICE: Do not solder the ends of wire connections to the drive. Soldered wiring connections can loosen
over time. Improper wiring practices could result in drive malfunction due to loose terminal connections.

Main Circuit Terminal Functions

Terminal
Type
R/L1
Main circuit power
S/L2
supply input
T/L3
U/T1
V/T2
Drive output
W/T3
B1
Braking resistor
B2
+1
DC reactor
connection
+2
+1
DC power supply
input
Ground
(2 terminals)

Wire Gauges and Tightening Torque

Select the appropriate wires and crimp terminals from
Note: 1. Wire gauge recommendations based on drive continuous current ratings using 75°C 600 Vac vinyl-
sheathed wire assuming ambient temperature within 30°C and wiring distance less than 100 m.
2. Terminals +1, +2, –, B1 and B2 are for connecting optional devices such as a DC reactor or braking
resistor. Do not connect other non-specified devices to these terminals.
• Consider the amount of voltage drop when selecting wire gauges.
Increase the wire gauge when the voltage drop is greater than 2% of motor rated voltage.
Ensure the wire gauge is suitable for the terminal block. Use the following formula to
calculate the amount of voltage drop:
• Line drop voltage (V) = 3 x wire resistance (Ω/km) x wire length (m) x current (A) x10
YASKAWA ELECTRIC TOEP C710606 09B YASKAWA AC Drive V1000 Installation & Start-Up Manual
Table 3.1 Main Circuit Terminal Functions
Connects line power to the drive.
Drives with single phase 200 V input power use terminals R/L1
and S/L2 only (T/L3 must not be used).
Connects to the motor.
Available for connecting a braking resistor or the braking resistor
unit option.
These terminals are shorted at shipment. Remove the shorting bar
between +1 and +2 when connecting to this terminal.
For connecting a DC power supply.
Grounding Terminal
For 200 V class: 100 Ω or less
For 400 V class: 10 Ω or less