4.7 Test Run
Press
to select LOCAL. The LO/RE light will turn on.
5.
Press
RUN
6.
on.
With SW1closed, the drive runs the motor at Multi-Step Speed 2
7.
(20 Hz).
With SW1 open and SW2 closed, the drive runs the motor at
8.
Multi-Step 3 (50 Hz).
With both SW1 and SW2 closed, the drive runs the motor at
9.
Multi-Step 4 (60 Hz).
Press
to stop the drive. The RUN light will flash until the
STOP
10.
motor comes to a complete stop.
<1> When the frequency reference is assigned to the LED operator (b1-01=0), the first step in a multi-step speed
sequence comes from d1-01.
<2> Set H3-10 (Multi-function Analog Input (current) Terminal A2 Function Selection) to "F" (not used).
Note: When a run command is input from the control circuit terminal, the frequency referenc value is
selected as follows: When b1-01 = 0 and the run command is given, the drive uses the frequency
set to d1-01. When b1-01 = 1 and the run command is given, the drive uses the frequency
reference value input to analog control terminal A1.
170
Step
to run the motor at 5 Hz. The RUN light will turn
YASKAWA ELECTRIC TOEP C710606 09B YASKAWA AC Drive V1000 Installation & Start-Up Manual
Display/Result
STOP
Off
STOP
Off
STOP
Flashing
On
On
Off