Multi-Step Speed Operation (4-Step Speed); Multi-Step Speed Operation Parameters; Digital Input; Wiring Example - YASKAWA V1000 Series Installation & Start-Up Manual

Compact vector control drive
Hide thumbs Also See for V1000 Series:
Table of Contents

Advertisement

4.7 Test Run
Turn the power on to the drive. The initial display appears.Note: Set
1.
the drive to REMOTE.
With multi-function contact input terminal S7 closed, the motor
2.
rotates forwards at 6 Hz.
Note: No run command is necessary when using the Jog frequency.
3.
The drive will stop with terminal S7 open.

Multi-Step Speed Operation (4-Step Speed)

Select up to 17 preset references (including Jog reference) using five multi-function inputs
S3 through S7. Four multi-step references can be selected using two multi-function inputs as
illustrated in
Figure

Multi-Step Speed Operation Parameters

No.
Name
d1-01
Frequency Reference 1
d1-02
Frequency Reference 2
d1-03
Frequency Reference 3
d1-04
Frequency Reference 4

Digital Input

Terminal
S5
S6

Wiring Example

Set up external switches SW1 and SW2.
168
Step
4.32.
Frequency reference. o1-03 determines the units, with Hz as the default.
Frequency reference when multi-function input "Multi-Step Speed Reference
1" (H1-
Frequency reference when multi-function input "Multi-Step Speed Reference
2" (H1-
Frequency reference when multi-function input "Multi-Step Speed Reference 1,
2" (H1-
Parameter
H1-05
H1-06
YASKAWA ELECTRIC TOEP C710606 09B YASKAWA AC Drive V1000 Installation & Start-Up Manual
Description
= 3) is on. Setting unit: set by o1-03.
= 4) is on. Setting unit: set by o1-03.
= 3 and 4) are both on. Setting unit: set by o1-03.
Setting
3
Multi-Step Speed Reference 1
4
Multi-Step Speed Reference 2
Display/Result
Motor
Contents