B.2 Parameter Table
No.
Name
H6-07
Pulse Train Monitor
Scaling
<22>
<22> Parameter can be changed during run.
<39> If this parameter is set to 0, the drive will be unable to respond to MEMOBUS/Modbus commands.
<40> The availability of certain functions depends on the control method used.
Note: Cycle power to the drive to enable MEMOBUS/Modbus settings.
L: Protection Function
L parameters provide protection to the drive and motor, such as: control during momentary
power loss, stall prevention, frequency detection, fault restarts, overtorque detection, torque
limits and other types of hardware protection.
No.
Name
Motor Overload
L1-01
Protection Selection
348
Sets the pulse output frequency in Hz when the
monitor value is 100%. Set H6-06 to "2" and
H6-07 to "0", to make the pulse train monitor
output equal to the output frequency.

L1: Motor Protection Functions

Use L1 parameters to configure motor protective functions.
Sets the motor thermal overload protection
(OL1) based on the cooling capacity of the
motor.
0: Disabled
1: Standard Fan Cooled (< 10:1 motor)
2: Standard Blower Cooled (≥ 10:1 motor)
3: Vector Motor (100:1 motor)
4: PM motor with variable torqueNOTICE:
The thermal protection is reset when the power
is cycled. In applications where the power is
frequently cycled, the drive may not be able to
provide protection, even if this parameter is set
to 1. Set to "0" and ensure each motor has a
thermal relay installed.
YASKAWA ELECTRIC TOEP C710606 09B YASKAWA AC Drive V1000 Installation & Start-Up Manual
Description
Description
Control
Mode
Range Def.
O
V/
P
L
f
M
V
0 to
1440
A A A
32000
Hz
Control
Mode
Range Def.
O
V/
P
L
f
M
V
1
0 to 4
S S S
<2>
Addr.
Pg.
Hex
432
Addr.
Pg.
Hex
480
146