LED Operator Display
Cause
The drive, control board, or terminal board has been
replaced and the parameter settings between the control
board and the terminal board no longer match.
LED Operator Display
Cause
Frequency reference is assigned to an option card
(b1-01 = 3) that is not connected to the drive.
The Run command is assigned to an option card
(b1-02 = 3) that is not connected to the drive.
Frequency reference is assigned to the pulse train input
(b1-01 = 4), but terminal RP is not set for pulse train input
(H6-01 is greater than 0).
LED Operator Display
Cause
H3-02 and H3-10 are set to the same value.
The following simultaneous contradictory settings:
H3-02 or H3-10 = B (PID Feedback)
H6-01 (Pulse Train Input) = 1 (PID Feedback)
The following simultaneous contradictory settings:H3-02
or H3-10 = C (PID Target Value)
H6-01 = 2 (pulse train input sets the PID target value)
The following simultaneous contradictory settings:H3-02
or H3-10 = C (PID Target Value)
b5-18 = 1 (enables b5-19 as the target PID value)
The following simultaneous contradictory settings:H6-01
or H3-10 = C (PID Target Value)
b5-18 = 1 (enables b5-19 as the target PID value)
YASKAWA ELECTRIC TOEP C710606 09B YASKAWA AC Drive V1000 Installation & Start-Up Manual
5.6 Operator Programming Errors
To load the parameter settings to the drive that are stored
in the terminal board, set A1-03 to 5550.
Initialize parameters after drive replacement by setting
A1-03 to 1110 or 2220.
Run Command Selection Error
oPE05
The Run command selection parameter b1-02 is set to 3
but no option board is installed.
Reconnect the option card to the drive.
Set H6-01 to "0".
Multi-Function Analog Input Selection Error
A contradictory setting is assigned to multi-function
oPE07
analog inputs H3-02 through to H3-10 and PID functions
conflict.
Change the settings to H3-02 and H3-10 so that functions
no longer conflict. Note: Both 0 (primary analog
frequency reference) and F (Not Used) can be set to
H3-02 and H3-10 at the same time.
Disable one of the PID selections.
Error Name
Possible Solutions
Error Name
Possible Solutions
Error Name
Possible Solutions
5
219