YASKAWA V1000 Series Installation & Start-Up Manual page 365

Compact vector control drive
Hide thumbs Also See for V1000 Series:
Table of Contents

Advertisement

No.
Name
Acceleration Pull-In
n8-51
Current
Voltage Error
n8-54
compensation time
constant
n8-55
Load Inertia
n8-62
Output voltage limit
<24>
<24> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<12> Default setting value is dependent on parameter o2-04, Drive/kVA Selection.
YASKAWA ELECTRIC TOEP C710606 09B YASKAWA AC Drive V1000 Installation & Start-Up Manual
Description
Sets the pull-in current during acceleration as a
percentage of the motor rated current (E5-03).
Set to a high value when more starting torque
is needed.
Sets the time constant for voltage error
compesation. Adjust the value when
• hunting occurs at low speed.
• hunting occurs with sudden load changes.
Increase in steps of 0.1 or disable the
compensation by setting n8-45 to 0.
• oscillations occur ar start. Increase the value
in steps of 0.1.
Sets the ratio between motor and machine
inertia.
0: less than 1:10.
1: between 1:10 to 1:30.
2: between 1:30 to 1:50.
3: higher than 1:50.
Sets the limit for the output voltage.
Adjustment is normally needed only if the
input voltage is below the n8-62 set value. In
this case set n8-62 to the input voltage.
B.2 Parameter Table
Control
Mode
Range Def.
Addr.
O
V/
P
Hex
L
f
M
V
0 to
50% − − A 53E
200%
0.00 to
1.00
− − A 56D
10.00 s
s
− − A 56E
0 to 3
0
0.0 to
200
- - A 57D
230.0
Vac
Pg.
B
365