B.2 Parameter Table
H2-
Function
Setting
Frequency (FOUT)
5
Detection 2
6
Drive Ready
7
DC Bus Undervoltage
8
During Baseblock
9
Option Reference
A
Local/Remote
Torque Detection 1
B
(N.O.)
C
Loss of Reference
D
Braking Resistor Fault
E
Fault
F
Not used
10
Alarm
Reset Command
11
Active
12
Timer Output
13
Fref/Fout Agree 2
14
Fref/Fset Agree 2
15
Frequency Detection 3
16
Frequency Detection 4
Torque Detection 1
17
(N.C.)
Torque Detection 2
18
(N.O.)
342
H2 Multi-Function Digital Output Settings
Closed: Output frequency is greater than or equal to the value in
L4-01, with hysteresis determined by L4-02.
Closed: Drive Ready. The drive is powered up, not in a fault state,
and in the Drive mode.
Closed: DC bus voltage is below the UV trip level set in L2-05.
Closed: This is no output voltage
Closed: Digital operator supplies the frequency reference.
Open: Reference 1 or 2 are active
Closed: Digital operator supplies the run command.
Closed: Output current/torque exceeds the torque value set in
parameter L6-02 for longer than the time set in parameter L6-03.
Closed: Loss of the analog frequency reference detected. Enabled
when L4-05 = 1.
Closed: Braking resistor or transistor is overheated or faulted out.
This selection requires that braking resistor protection parameter
be set for ERF (L8-01 = "1").
Closed: Fault occurred (other than CPF00 and CPF01).
Set this value when the terminal is not used, or when using the
terminal in the pass-through mode.
Closed: An alarm is triggered.
Closed: Reset command to the drive is active.
Timer output, controlled by b4-01 and b4-02. Used in conjunction
with the digital input (H1-
Closed: When drive output frequency equals the frequency
reference +/- L4-04.
Closed: When the drive output frequency is equal to the value in
L4-03 (plus or minus L4-04).
Closed: When the drive output frequency is less than or equal to
the value in L4-03 with the hysteresis determined by L4-04.
Closed: When the output frequency is greater than or equal to the
value in L4-03 with the hysteresis determined by L4-04.
Open: When the output current/torque exceeds the value set in
parameter L6-02 for more time than is set in parameter L6-03.
Closed: When the output current/torque exceeds the value set in
parameter L6-05 for more time than is set in parameter L6-06.
YASKAWA ELECTRIC TOEP C710606 09B YASKAWA AC Drive V1000 Installation & Start-Up Manual
Description
= 18 "timer function").
Control
Mode
Pg.
O
V/
P
L
f
M
V
O O O —
O O O —
O O O —
O O O —
O O O —
O O O —
O O O —
O O O —
O O O —
O O O —
O O O —
O O O —
O O O —
O O O —
O O O —
O O O —
O O O —
O O O —
O O O —
O O O —