Drive Model CIMR-V
4A0018
4A0023
4A0031
4A0038

Guarding Against Harmful Materials

When installing IP20/Open-Chassis drives, use an enclosure that prevents foreign material
from entering the drive from above or below.
Grounding
The drive is designed to be used in T-N (grounded neutral point) networks. If installing the
drive in other types of grounded systems, contact your dealer or Yaskawa for instructions.

EMC Guidelines Compliance

This drive is tested according to European standards EN61800-3 and it complies with the
EMC guidelines.
EMC Filter Installation
The following conditions must be met to ensure continued compliance with guidelines.
• EMC Filter Selection: Refer to Yaskawa catalog for EMC filter selection.
• EMC Filter Installation: Refer to option manual for option installation instructions.
Installation Method
Verify the following installation conditions to ensure that other devices and machinery used
in combination with this drive also comply with EMC guidelines.
1.
Install an EMC noise filter to the input side specified by Yaskawa for compliance
with European standards.
2.
Place the drive and EMC noise filter in the same enclosure.
3.
Use braided shield cable for the drive and motor wiring or run the wiring through a
metal conduit.
4.
Keep wiring as short as possible. Ground the shield on both the drive side and the
motor side.
YASKAWA ELECTRIC TOEP C710606 09B YASKAWA AC Drive V1000 Installation & Start-Up Manual
Time Delay/
Class RK5 Fuses
Fuse Ampere Rating
600 Vac, 200 kAIR
Not Available
D.2 European Standards
Non-Time Delay/
Class T Fuses
600 Vac, 200 kAIR
50
60
70
80
A6T50
A6T60
A6T70
A6T80
D