Sequence Circuit Design For Opening And Closing The Holding Brake; Holding Brake Circuit Design - YASKAWA V1000 Series Installation & Start-Up Manual

Compact vector control drive
Hide thumbs Also See for V1000 Series:
Table of Contents

Advertisement

Brake Open/Close
Function
Parameter
Frequency
L4-07 = 0
Detection 2
H2-03 = 5
<1> This setting range is available when using OLV Control. In V/f Control, set the level as the motor rated slip
frequency pulse 0.5 Hz. Not enough motor torque will be created if this value is set too low, and the load may tend
to slip. Make sure this value greater than the minimum output frequency and greater than the value of L4-02 as
shown in the diagram below. If this value is set too high, there may be a jolt at start.
<2> Adjust Hysteresis for Frequency Detection 2 by changing the frequency detection width (L4-02) between 0.0 and
0.5 Hz. If the load slips during stop, make incremental changes of 0.1 Hz until the load no longer slips.
Output
Frequency
Frequency
Detection 2

Sequence Circuit Design for Opening and Closing the Holding Brake

Design the braking sequence as follows:
The brake should release when terminal P2-PC closes in response to the run conditions on
the sequence side.
When a fault signal is output, the brake should close. When an up or down command is
entered, the brake should release.
Figure 4.10
UP
S1
Forward
DOWN
S2
Reverse
High speed
S6
Multi-step speed 2)
Low speed
SC
YASKAWA ELECTRIC TOEP C710606 09B YASKAWA AC Drive V1000 Installation & Start-Up Manual
Brake Activation Level
Signal
Frequency Detection Level
Frequency Detection Width
L4-01
Drive
Fault Contact
MA
MB
MC
Frequency Detect 2
P2
PC
Figure 4.10 Holding Brake Circuit Design
4.5 Application Presets
Parameter
L4-01 = 1.0 to 3.0 Hz
L4-02 = 0.0 to 0.5 Hz
L4-02
ON
OFF
Holding brake
auxilary relay coil
UP
Safety
Circuit
DOWN
BR
ON Brake energized
DC 30V 1 A
Control Mode
OLV for
V/f
OLV
PM
<1>
O
O
<2>
Time
24 V
BR
-
4
119