Motor Does Not Operate When An External Run Command Is Input; Motor Stops During Acceleration Or When A Load Is Connected - YASKAWA V1000 Series Installation & Start-Up Manual

Compact vector control drive
Hide thumbs Also See for V1000 Series:
Table of Contents

Advertisement

5.9 Troubleshooting without Fault Display
Pressed
Cause
The LOCAL/REMOTE mode is not
selected properly.
The drive is not in drive mode.
The frequency reference is too low.

Motor Does Not Operate When an External Run Command is Input

Cause
The LOCAL/REMOTE mode is not
selected properly.
The drive is not in Drive Mode.
The frequency reference is too low.

Motor Stops During Acceleration or When a Load is Connected

Cause
• The load is too heavy.
• The limit of motor response may be
reached during rapid acceleration. This
may be a result of improper stall
prevention or automatic torque boost
function adjustment. (L3-01 = 2)
Motor Rotates in One Direction Only
Cause
"Reverse run prohibited" is selected. If
b1-04 (Reverse Prohibit Operation) is set
to 1 (reverse run prohibited), the drive
will not accept a reverse run command.
240
Press the LOCAL/REMOTE button to switch. The LO/RE LED should be
on for LOCAL mode.
A run command will not be issued. Exit to the drive mode and cycle the
run command.
• If the frequency reference is set below the frequency set in E1-09
(Minimum Output Frequency), the drive will not operate.
• Raise the frequency reference to at least the minimum output frequency.
Press the LOCAL/REMOTE button to switch. The LO/RE LED should be
off for REMOTE mode.
A run command will not be issued. Exit to the Drive mode and cycle the
run command.
• If the frequency reference is set below the frequency set in E1-09
(Minimum Output Frequency), the drive will not operate.
• Raise the frequency reference to at least the minimum output frequency.
Increase the acceleration time (C1-01) or reduce the motor load. Also,
consider increasing the motor size and/or drive size.
Set b1-04 = "0" to allow reverse run operation.
YASKAWA ELECTRIC TOEP C710606 09B YASKAWA AC Drive V1000 Installation & Start-Up Manual
Possible Solutions
Possible Solutions
Possible Solution
Possible Solution