3 Wiring and Connection

3.8.3 Connecting a Reactor for Harmonic Suppression

Connect the noise filter ground wire directly to the ground plate.
Do not connect the noise filter ground wire to other ground wires.
Ground plate
If a noise filter is located inside a control panel, first connect the noise filter ground wire and the
ground wires from other devices inside the control panel to the ground plate for the control panel,
then ground the plates.
Ground
3.8.3

Connecting a Reactor for Harmonic Suppression

The SERVOPACK has reactor connection terminals for power supply harmonic suppression that can be used
as required. The reactor is an optional part. You must acquire it separately. For reactor selection and specifica-
tions, refer to the
Connect a reactor as shown in the following diagram.
SERVOPACK with 100-VAC Power Input
Power
supply
Note 1. Connection terminals for DC reactor
2. DC reactors cannot be connected to SERVOPACKs with a single-phase 100-V power input.
3-36
Incorrect
Noise
Filter
SERVOPACK SERVOPACK
Shielded
ground wire
Ground plate
Control Panel
Noise
Filter
Ground plate
Σ
-V Series Product Catalog (Catalog No.: KAEP S800000 42).
AC reactor
short-circuit, and connect a DC reactor.
Correct
Noise
Filter
SERVOPACK SERVOPACK
SERVOPACK
SERVOPACK
SERVOPACK with 200/400-VAC Power Input
SERVOPACK
L1
L2
1 and
2 are short-circuited at shipment. Remove the lead wire for
SERVOPACK
DC reactor
1
2