3 Wiring and Connection
3.1.2 Using a Standard Power Supply (Single-phase 100 V, Three-phase 200 V, or Three-phase 400 V)
2. The following restrictions apply to UL standard compliance conditions.
3-10
SERVOPACK Model SGDV-
180A, 200A
330A
470A, 550A
590A, 780A
210D, 260D
280D, 370D
Available rated current for modeled-case circuit breaker: 40 A or less
• Available rated current for non-time delay fuse: 70 A or less
• Available rated current for time delay fuse: 40 A or less
• Do not use single wires.
• Available rated current for molded-case circuit breaker: 60 A or less
• Available rated current for non-time delay fuse or time delay fuse: 60 A or
less
• Available rated current for molded-case circuit breaker: 100 A or less.
• Available rated current for non-time delay fuse or time delay fuse: 100 A or
less
(Available rated current for a non-time delay, Class J fuse or a faster fuse: 125
A or less)
• Available rated current for molded-case circuit breaker: 60 A or less.
• Available rated current for non-time-delay fuse: 60 A or less.
• Available rated current for time delay fuse: 35 A or less
• Available rated current for molded-case circuit breaker: 80 A or less
• Available rated current for non-time delay fuse: 125 A or less
• Available rated current for time delay fuse: 75 A or less