YASKAWA SGMJV User Manual page 195

Rotational motor mechatrolink-ii communications reference
Hide thumbs Also See for SGMJV:
Table of Contents

Advertisement

5 Adjustments
5.5.2 One-parameter Tuning Procedure
Step
8
9
10
11
Note: The status display will always be RUN when the servomotor power is ON.
5-40
Display after Operation
Keys
If readjustment is required, select the digit with the
or
Key or change the FF LEVEL and FB
LEVEL with the
response.
Refer to 5.5.3 One-parameter Tuning Example for
details.
If readjustment is not required, go to step 9.
Note: The higher the FF LEVEL, the positioning time
will be shorter and the response will be better.
If the level is too high, however, overshooting
or vibration may occur. Overshooting will be
reduced if the FB LEVEL is increased.
<NOTE>
• If the FF LEVEL is changed when the servomotor
is in operation, it will not be reflected immediately.
The changes will be effective after the servomotor
comes to a stop with no reference input and then
the servomotor starts operation.
If the FF LEVEL is changed too much during oper-
ation, vibration may occur because the responsive-
ness changes rapidly when the settings become
effective.
• The message "FF LEVEL" flashes until the SER-
VOPACK reaches the effective FF LEVEL. If the
servomotor does not stop within approximately 10
seconds after changing the setting, a timeout will
occur. The setting will be returned to the previous
value.
 If Vibration Occurs
• If vibration occurs, press the
VOPACK will automatically detect the vibration
frequencies and set the notch filters or anti-reso-
nance control. When the notch filter is set, "NF1"
and "NF2" are displayed on the bottom row. When
the anti-resonance control is set, "ARES" will be
displayed on the bottom row.
 If Vibration Is Large
• Even if the
PACK will automatically detect the vibration fre-
quencies and make notch filter or anti-resonance
control settings.
Press the
Key to display the confirmation screen
after level adjustment.
• Press the
After the data is saved, "DONE" will flash for
approximately two seconds and then "RUN" will
be displayed.
• To return to the previous value, press the
• Press the
saving the values.
Press the
tuning operation. The screen in step 1 will appear
again.
Operation
or
Key. Check the
Key. The SER-
Key is not pressed, the SERVO-
Key to save the adjusted values.
Key to readjust the level without
Key to complete the one-parameter
(cont'd)
Key.