Interface Alarm Messages

Copyright © 2017, Juniper Networks, Inc.
Table 66: Chassis Component Alarm Conditions on QFX10000 Modular
Models (continued)
Chassis
Component
Alarm Condition
Temperature
The chassis temperature
has exceeded 131° F
(55° C), the fans have
been turned on to full
speed, and one or more
fans have failed.
The chassis temperature
has exceeded 149° F
(65° C), and the fans
have been turned on to
full speed.
The chassis temperature
has exceeded 149° F
(65° C), and a fan has
failed. If this condition
persists for more than 4
minutes, the switch will
shut down.
Chassis temperature has
exceeded 167° F (75° C).
If this condition persists
for more than 4 minutes,
the switch will shut down.
The temperature sensor
has failed.
Configuring the Junos OS to Determine Conditions That Trigger Alarms on Different
Interface Types
alarm
Interface alarms are alarms that you configure to alert you when an interface is down.
To configure an interface link-down condition to trigger a red or yellow alarm, or to
configure the link-down condition to be ignored, use the
chassis
] hierarchy level. You can specify the
interface type.
management-ethernet
Chapter 26: Alarm Messages
Alarm
Severity
Remedy
Minor
Check room temperature.
(yellow)
Check airflow.
Replace the fan tray.
Minor
Check room temperature.
(yellow)
Check airflow.
Check the fans.
Major
Check room temperature.
(red)
Check airflow.
Check the fan.
Major
Check room temperature.
(red)
Check airflow.
Check fan.
Major
Open a support case using the Case
(red)
Manager link at
http://www.juniper.net/support/
or call 1-888-314-5822 (toll free, US
& Canada) or 1-408-745-9500 (from
outside the United States).
statement at the [
alarm
ethernet
,
fibre-channel
, or
edit