Test Mode Functionality Testmode; Identification; Functionality - ABB RET650 Technical Manual

Relion 650 series transformer protection
Hide thumbs Also See for RET650:
Table of Contents

Advertisement

Section 17
Basic IED functions
17.4
17.4.1
17.4.2
574
IEC09000063 V1 EN
Figure 255:
Connection of the function to external circuits
The above example also shows the five output signals, GRP1 to 4 for confirmation of
which group that is active, and the SETCHGD signal which is normally connected to
a SP16GGIO function block for external communication to higher level control
systems.

Test mode functionality TESTMODE

Identification

Function description
Test mode functionality

Functionality

When the Test mode functionality TESTMODE is activated, all the functions in the
IED are automatically blocked. Activated TESTMODE is indicating by a flashing
yellow LED on the local HMI. It is then possible to unblock every function(s)
individually from the local HMI to perform required tests.
When leaving TESTMODE, all blockings are removed and the IED resumes normal
operation. However, if during TESTMODE operation, power is removed and later
restored, the IED will remain in TESTMODE with the same protection functions
blocked or unblocked as before the power was removed. All testing will be done with
ACTIVATE GROUP 4
ACTIVATE GROUP 3
ACTIVATE GROUP 2
ACTIVATE GROUP 1
IOx-Bly1
Æ
IOx-Bly2
Æ
IOx-Bly3
Æ
IOx-Bly4
Æ
IEC 61850
IEC 60617
identification
identification
TESTMODE
1MRK 504 135-UEN A
ACTVGRP
ACTGRP1
GRP1
ACTGRP2
GRP2
ACTGRP3
GRP3
GRP4
ACTGRP4
SETCHGD
IEC09000063_en_1.vsd
ANSI/IEEE C37.2
device number
-
-
Technical manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents