Function Commands For Iec 60870-5-103 I103Cmd; Functionality; Function Block; Signals - ABB RET650 Technical Manual

Relion 650 series transformer protection
Hide thumbs Also See for RET650:
Table of Contents

Advertisement

Section 12
Control
12.9
12.9.1
12.9.2
12.9.3
364
appropriate. ex: pulse-On, on-time=100, off-time=300, count=5 would give 5 positive
100 ms pulses, 300 ms apart.
There is a BLOCK input signal, which will disable the operation of the function, in the
same way the setting Operation: On/Off does. That means that, upon activation of the
BLOCK input, all 32 CMDBITxx outputs will be set to 0. The BLOCK acts like an
overriding, the function still receives data from the DNP3 master. Upon deactivation
of BLOCK, all the 32 CMDBITxx outputs will be set by the DNP3 master again,
momentarily. For AUTOBITS , the PSTO input determines the operator place. The
command can be written to the block while in "Remote". If PSTO is in "Local" then
no change is applied to the outputs.
For description of the DNP3 protocol implementation, refer to DNP3 communication
protocol manual.

Function commands for IEC 60870-5-103 I103CMD

Functionality

I103CMD is a command function block in control direction with pre-defined output
signals. The signals are in steady state, not pulsed, and stored in the IED in case of
restart.

Function block

I103CMD
BLOCK
16-AR
17-DIFF
18-PROT
IEC10000282-1-en.vsd
IEC10000282 V1 EN
Figure 158:
I103CMD function block

Signals

Table 260:
I103CMD Input signals
Name
Type
BLOCK
BOOLEAN
Table 261:
I103CMD Output signals
Name
Type
16-AR
BOOLEAN
17-DIFF
BOOLEAN
18-PROT
BOOLEAN
Default
Description
0
Block of commands
Description
Information number 16, off/on of autorecloser
Information number 17, block of differential
protection
Information number 18, block of protection
1MRK 504 135-UEN A
Technical manual