Function Block; Signals - ABB RET650 Technical Manual

Relion 650 series transformer protection
Hide thumbs Also See for RET650:
Table of Contents

Advertisement

Section 14
Monitoring
14.22.2
14.22.3
518

Function block

I103FLTPROT
BLOCK
64_STL1
65_STL2
66_STL3
67_STIN
68_TRGEN
69_TRL1
70_TRL2
71_TRL3
72_TRBKUP
73_SCL
74_FW
75_REV
76_TRANS
77_RECEV
78_ZONE1
79_ZONE2
80_ZONE3
81_ZONE4
82_ZONE5
84_STGEN
85_BFP
86_MTRL1
87_MTRL2
88_MTRL3
89_MTRN
90_IOC
91_IOC
92_IEF
93_IEF
ARINPROG
FLTLOC
IEC10000291-1-en.vsd
IEC10000291 V1 EN
Figure 231:
I103FLTPROT function block

Signals

Table 423:
I103FLTPROT Input signals
Name
Type
BLOCK
BOOLEAN
64_STL1
BOOLEAN
65_STL2
BOOLEAN
66_STL3
BOOLEAN
67_STIN
BOOLEAN
68_TRGEN
BOOLEAN
69_TRL1
BOOLEAN
70_TRL2
BOOLEAN
71_TRL3
BOOLEAN
72_TRBKUP
BOOLEAN
73_SCL
REAL
74_FW
BOOLEAN
75_REV
BOOLEAN
Table continues on next page
Default
Description
0
Block of status reporting.
0
Information number 64, start phase L1
0
Information number 65, start phase L2
0
Information number 66, start phase L3
0
Information number 67, start residual current IN
0
Information number 68, trip general
0
Information number 69, trip phase L1
0
Information number 70, trip phase L2
0
Information number 71, trip phase L3
0
Information number 72, back up trip I>>
0
Information number 73, fault location in ohm
0
Information number 74, forward/line
0
Information number 75, reverse/busbar
1MRK 504 135-UEN A
Technical manual