Impedance protection
Power swing detection ZMRPSB
Identification
Function description
Power swing detection
Functionality
Power swings may occur after disconnection of heavy loads or trip of big generation
plants.
Power swing detection function ZMRPSB is used to detect power swings and initiate
block of all distance protection zones. Occurrence of earth-fault currents during a
power swing inhibits the ZMRPSB function to allow fault clearance.
Function block
ZMRPSB