Function Block; Signals; Settings; Ied Commands With Position And Select For Iec 60870-5-103 - ABB RET650 Technical Manual

Relion 650 series transformer protection
Hide thumbs Also See for RET650:
Table of Contents

Advertisement

Section 12
Control
12.12.2
12.12.3
12.12.4
Table 271:
I103GENCMD Non group settings (basic)
Name
FunctionType
PulseLength
InfNo
12.13
12.13.1
368

Function block

I103GENCMD
BLOCK
^CMD_OFF
^CMD_ON
IEC10000285-1-en.vsd
IEC10000285 V1 EN
Figure 161:
I103GENCMD function block

Signals

Table 269:
I103GENCMD Input signals
Name
BLOCK
Table 270:
I103GENCMD Output signals
Name
CMD_OFF
CMD_ON

Settings

Values (Range)
Unit
1 - 255
-
0.000 - 60.000
s
1 - 255
-
IED commands with position and select for IEC

60870-5-103 I103POSCMD

Functionality

I103POSCMD has double-point position indicators that are getting the position value
as an integer (for example from the POSITION output of the SCSWI function block)
and sending it over IEC 60870-5-103 (1=OPEN; 2=CLOSE). .The standard does not
define the use of values 0 and 3 . However, when connected to a switching device,
these values are transmitted.
Type
Default
Description
BOOLEAN
0
Block of command
Type
Description
BOOLEAN
Command output OFF
BOOLEAN
Command output ON
Step
Default
1
1
0.001
0.400
1
1
1MRK 504 135-UEN A
Description
Function type (1-255)
Pulse length
Information number for command output
(1-255)
Technical manual