Section 11
Secondary system supervision
11.1.3
11.1.4
244

Function block

SDDRFUF
I3P*
BLKZ
U3P*
BLKU
BLOCK
3PH
CBCLOSED
DLD1PH
MCBOP
DLD3PH
DISCPOS
IEC08000220 V1 EN
Figure 110:
SDDRFUF function block

Signals

Table 168:
SDDRFUF Input signals
Name
Type
I3P
GROUP
SIGNAL
U3P
GROUP
SIGNAL
BLOCK
BOOLEAN
CBCLOSED
BOOLEAN
MCBOP
BOOLEAN
DISCPOS
BOOLEAN
Table 169:
SDDRFUF Output signals
Name
Type
BLKZ
BOOLEAN
BLKU
BOOLEAN
3PH
BOOLEAN
DLD1PH
BOOLEAN
DLD3PH
BOOLEAN
Default
Description
-
Three phase group signal for current inputs
-
Three phase group signal for voltage inputs
0
Block of function
0
Active when circuit breaker is closed
0
Active when external MCB opens protected voltage
circuit
0
Active when line disconnector is open
Description
Start of current and voltage controlled function
General start of function
Three-phase start of function
Dead line condition in at least one phase
Dead line condition in all three phases
1MRK 504 135-UEN A
Technical manual

Hide quick links:

Advertisement