Settings; Monitored Data - ABB RET650 Technical Manual

Relion 650 series transformer protection
Hide thumbs Also See for RET650:
Table of Contents

Advertisement

Section 6
Differential protection
6.2.5
6.2.6
112
Signal
IDIFF
ANGLE
I2RATIO

Settings

Table 38:
Basic general settings for the function REFPDIF (REF1-)
Parameter
Range
GlobalBaseSel
1 - 6
Table 39:
Basic parameter group settings for the function REFPDIF (REF1-)
Parameter
Range
Operation
Off
On
IdMin
4.0 - 100.0
Table 40:
Advanced parameter group settings for the function REFPDIF (REF1-)
Parameter
Range
ROA
60 - 90

Monitored data

Table 41:
REFPDIF Monitored data
Name
Type
IRES
REAL
IN
REAL
IBIAS
REAL
IDIFF
REAL
ANGLE
REAL
I2RATIO
REAL
Description
Magnitude of fundamental frequency differential current
Direction angle from zero sequence feature
Second harmonic ratio
Step
Default
1
1
Step
Default
-
Off
0.1
10.0
Step
Default
1
60
Values (Range)
Unit
-
A
-
A
-
A
-
A
-
deg
-
-
1MRK 504 135-UEN A
Unit
Description
-
Selection of one of
the Global Base
Value groups
Unit
Description
-
Operation Off / On
%IB
Maximum sensitivity
in % of IBase
Unit
Description
Deg
Relay operate angle
for zero sequence
directional feature
Description
Magnitude of
fundamental frequency
residual current
Magnitude of
fundamental frequency
neutral current
Magnitude of the bias
current
Magnitude of
fundamental frequency
differential current
Direction angle from zero
sequence feature
Second harmonic ratio
Technical manual