ABB RET650 Technical Manual page 259

Relion 650 series transformer protection
Hide thumbs Also See for RET650:
Table of Contents

Advertisement

1MRK 504 135-UEN A
Technical manual
Fuse failure detection
Main logic
TEST
TEST ACTIVE
AND
BlocFuse = Yes
BLOCK
All UL < USealIn<
SealIn = On
Any UL < UsealIn<
FuseFailDetDUDI
AND
OpDUDI = On
FuseFailDetZeroSeq
AND
AND
FuseFailDetNegSeq
AND
UNsINs
UZsIZs
UZsIZs OR UNsINs
OpMode
UZsIZs AND UNsINs
OptimZsNs
CurrZeroSeq
a
a>b
CurrNegSeq
b
DeadLineDet1Ph
MCBOP
60 sec
t
All UL > UsealIn<
VoltZeroSeq
OR
VoltNegSeq
AllCurrLow
CBCLOSED
DISCPOS
IEC10000041 V1 EN
Figure 114:
Simplified logic diagram for fuse failure supervision function, Main
logic
Secondary system supervision
OR
OR
AND
AND
5 s
OR
t
OR
OR
AND
AND
200 ms
AND
t
150 ms
t
OR
AND
5 sec
t
Section 11
intBlock
AND
AND
AND
OR
AND
OR
IEC10000041-1-en.vsd
BLKZ
BLKU
253

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents