ABB RET650 Technical Manual page 406

Relion 650 series transformer protection
Hide thumbs Also See for RET650:
Table of Contents

Advertisement

Section 13
Logic
400
This follows the general formulae: The sum of the values of all OUTx = 2
1≤x≤16 will be equal to the integer value on the input INP.
The Integer to Boolean 16 conversion function (IB16A) will transfer an integer with
a value between 0 to 65535 connected to the input INP to a combination of activated
outputs OUTx where 1≤x≤16. The sum of the values of all OUTx will then be equal
to the integer on input INP. The values of the different OUTx are according to the table
below. When an OUTx is not activated, its value is 0.
When all OUTx where 1≤x≤16 are activated that is = Boolean 1 it corresponds to that
integer 65535 is connected to input INP. The IB16A function is designed for receiving
the integer input locally. If the BLOCK input is activated, it will freeze the logical
outputs at the last value.
Values of each of the different OUTx from function block IB16A for 1≤x≤16.
The sum of the value on each INx corresponds to the integer presented on the output
OUT on the function block IB16A.
Name of OUTx
Type
OUT1
BOOLEAN
OUT2
BOOLEAN
OUT3
BOOLEAN
OUT4
BOOLEAN
OUT5
BOOLEAN
OUT6
BOOLEAN
OUT7
BOOLEAN
OUT8
BOOLEAN
OUT9
BOOLEAN
OUT10
BOOLEAN
OUT11
BOOLEAN
OUT12
BOOLEAN
OUT13
BOOLEAN
OUT14
BOOLEAN
OUT15
BOOLEAN
OUT16
BOOLEAN
The sum of the numbers in column "Value when activated" when all OUTx (where x
= 1 to 16) are active that is=1; is 65535. 65535 is the highest integer that can be
converted by the IB16A function block.
Description
Value when
activated
Output 1
1
Output 2
2
Output 3
4
Output 4
8
Output 5
16
Output 6
32
Output 7
64
Output 8
128
Output 9
256
Output 10
512
Output 11
1024
Output 12
2048
Output 13
4096
Output 14
8192
Output 15
16384
Output 16
32768
1MRK 504 135-UEN A
x-1
where
Value when
deactivated
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Technical manual