Technical Data; Restricted Earth-Fault Protection, Low Impedance Refpdif; Identification - ABB RET650 Technical Manual

Relion 650 series transformer protection
Hide thumbs Also See for RET650:
Table of Contents

Advertisement

Section 6
Differential protection
6.1.5
6.2
6.2.1
110

Technical data

Table 35:
T2WPDIF, T3WPDIF technical data
Function
Operating characteristic
Reset ratio
Unrestrained differential current limit
Base sensitivity function
Minimum negative sequence current
Operate angle, negative sequence
Second harmonic blocking
Fifth harmonic blocking
Connection type for each of the windings
Phase displacement between high voltage
winding, W1 and each of the windings, W2
and W3. Hour notation
Operate time, restrained function
Reset time, restrained function
Operate time, unrestrained function
Reset time, unrestrained function
Restricted earth-fault protection, low impedance
REFPDIF

Identification

Function description
Restricted earth-fault protection, low
impedance
Range or value
Adaptable
>94%
IBase on
(1.00-50.00)x
high voltage winding
IBase
(0.05 - 0.60) x
IBase
(0.02 - 0.20) x
(30.0 - 90.0) degrees
(5.0-100.0)% of
fundamental differential
current
(5.0-100.0)% of
fundamental differential
current
Y or D
0–11
25 ms typically at 0 to 5
x set level
25 ms typically at 5 to 0
x set level
20 ms typically at 0 to 5
x set level
25 ms typically at 5 to 0
x set level
IEC 61850
IEC 60617
identification
identification
REFPDIF
IdN/I
SYMBOL-AA V1 EN
1MRK 504 135-UEN A
Accuracy
± 1.0% of Ir for I < Ir
± 1.0% of I for I > Ir
-
± 1.0% of set value
± 1.0% of Ir
± 1.0% of Ir
± 1.0 degrees
± 2.0% of applied harmonic
magnitude
± 12.0% of applied harmonic
magnitude
-
-
-
-
-
-
ANSI/IEEE C37.2
device number
87N
Technical manual