Monitored Data; Operation Principle - ABB RET650 Technical Manual

Relion 650 series transformer protection
Hide thumbs Also See for RET650:
Table of Contents

Advertisement

Section 8
Current protection
Name
CurrMult_OC2
tDef_OC2
DirMode_OC2
DirPrinc_OC2
ActLowVolt2_VM
Table 127:
DNSPTOC Non group settings (basic)
Name
GlobalBaseSel
8.9.6
8.9.7
200
Values (Range)
Unit
1.0 - 10.0
-
0.00 - 6000.00
s
Non-directional
-
Forward
Reverse
I&U
-
IcosPhi&U
Non-directional
-
Block
Values (Range)
Unit
1 - 6
-

Monitored data

Table 128:
DNSPTOC Monitored data
Name
CURRENT
VOLTAGE
UIANGLE

Operation principle

Negative sequence based overcurrent function (DNSPTOC) has two settable current
levels, setting parameters StartCurr_OC1 and StartCurr_OC2. Both features have
definite time characteristics with settings tDef_OC1 and tDef_OC2 respectively. It is
possible to change the direction of these steps to forward, reverse or non-directional
by setting parameters DirMode_OC1 and DirMode_OC2. At too low polarizing
voltage the overcurrent feature can be either blocked or non-directional. This is
controlled by settings ActLowVolt1_VM and ActLowVolt2_VM.
Step
Default
0.1
2.0
0.01
0.50
-
Non-directional
-
I&U
-
Block
Step
Default
1
1
Type
Values (Range)
REAL
-
REAL
-
REAL
-
1MRK 504 135-UEN A
Description
Multiplier for current operate level for step
2 (OC2)
Independent (definite) time delay for step
2 (OC2)
Directional mode of step 2 (non-
directional, forward, reverse)
Measuring on I & U or IcosPhi & U for step
2 (OC2)
Low votlage level action for step 2 (Non-
directional, Block, Memory)
Description
Selection of one of the Global Base Value
groups
Unit
Description
A
Measured current value
kV
Measured voltage value
deg
Angle between voltage
and current
Technical manual