Settings; Functionality - ABB RET650 Technical Manual

Relion 650 series transformer protection
Hide thumbs Also See for RET650:
Table of Contents

Advertisement

1MRK 504 135-UEN A
12.11.4
Table 268:
I103USRCMD Non group settings (basic)
Name
Values (Range)
FunctionType
PulseMode
PulseLength
InfNo_1
InfNo_2
InfNo_3
InfNo_4
InfNo_5
InfNo_6
InfNo_7
InfNo_8
12.12
12.12.1
Technical manual
Name
OUTPUT6
OUTPUT7
OUTPUT8

Settings

Unit
1 - 255
-
Steady
-
Pulsed
0.200 - 60.000
s
1 - 255
-
1 - 255
-
1 - 255
-
1 - 255
-
1 - 255
-
1 - 255
-
1 - 255
-
1 - 255
-
Function commands generic for IEC 60870-5-103
I103GENCMD

Functionality

I103GENCMD is used for transmitting generic commands over IEC 60870-5-103.
The function has two outputs signals CMD_OFF and CMD_ON that can be used to
implement double-point command schemes.
The I103GENCMD component can be configured as either 2 pulsed ON/OFF or 2
steady ON/OFF outputs. The ON output is pulsed with a command with value 2, while
the OFF output is pulsed with a command value 1. If in steady mode is ON asserted
and OFF deasserted with command 2 and vice versa with command 1. The
I103GENCMD is retained, and a command in steady mode will be reissued on restart.
The standard does not define the use of values 0 and 3. However, when connected to
a switching device, these values are transmitted.
Type
Description
BOOLEAN
Command output 6
BOOLEAN
Command output 7
BOOLEAN
Command output 8
Step
Default
1
1
-
Pulsed
0.001
0.400
1
1
1
2
1
3
1
4
1
5
1
6
1
7
1
8
Section 12
Description
Function type (1-255)
Pulse mode
Pulse length
Information number for output 1 (1-255)
Information number for output 2 (1-255)
Information number for output 3 (1-255)
Information number for output 4 (1-255)
Information number for output 5 (1-255)
Information number for output 6 (1-255)
Information number for output 7 (1-255)
Information number for output 8 (1-255)
Control
367