Functionality; Function Block; Signals; Settings - ABB RET650 Technical Manual

Relion 650 series transformer protection
Hide thumbs Also See for RET650:
Table of Contents

Advertisement

Section 16
Station communication
16.7.2
16.7.3
16.7.4
16.7.5
Table 456:
GOOSEDPRCV Non group settings (basic)
Name
Operation
16.7.6
544

Functionality

GOOSEDPRCV is used to receive a double point value using IEC61850 protocol via
GOOSE.

Function block

GOOSEDPRCV
BLOCK
DATAVALID
COMMVALID
IEC10000249-1-en.vsd
IEC10000249 V1 EN
Figure 242:
GOOSEDPRCV function block

Signals

Table 454:
GOOSEDPRCV Input signals
Name
BLOCK
Table 455:
GOOSEDPRCV Output signals
Name
DPOUT
DATAVALID
COMMVALID
TEST

Settings

Values (Range)
Unit
Off
-
On

Operation principle

The DATAVALID output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total
failure condition and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
^DPOUT
TEST
Type
Default
Description
BOOLEAN
0
Type
Description
INTEGER
BOOLEAN
BOOLEAN
BOOLEAN
Step
Default
-
Off
1MRK 504 135-UEN A
Block of function
Double point output
Data valid for double point output
Communication valid for double point output
Test output
Description
Operation Off/On
Technical manual