Technical Data - ABB RET650 Technical Manual

Relion 650 series transformer protection
Hide thumbs Also See for RET650:
Table of Contents

Advertisement

Section 15
Metering
15.2.8
532
Outputs are available for forward as well as reverse direction. The accumulated
energy values can be reset from the local HMI reset menu or with input signal
RSTACC.
The maximum demand values for active and reactive power are calculated for the set
time interval tEnergy. The maximum values are updated every minute and stored in a
register available over communication and from outputs MAXPAFD, MAXPARD,
MAXPRFD, MAXPRRD for the active and reactive power forward and reverse
direction until reset with input signal RSTDMD or from the local HMI reset menu.
CVMMXN
P_INST
Q_INST
TRUE
FALSE
FALSE
IEC09000106 V1 EN
Figure 238:
Connection of Energy calculation and demand handling function
(ETPMMTR) to the Measurements function (CVMMXN)

Technical data

Table 441:
ETPMMTR technical data
Function
Energy metering
ETPMMTR
P
Q
STACC
RSTACC
RSTDMD
IEC09000106.vsd
Range or value
MWh Export/Import, MVArh
Export/Import
1MRK 504 135-UEN A
Accuracy
Input from MMXU. No extra
error at steady load
Technical manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents