ABB RET650 Technical Manual page 628

Relion 650 series transformer protection
Hide thumbs Also See for RET650:
Table of Contents

Advertisement

Section 20
IED and functionality tests
622
Description
Continuous
Pulse magnetic field immunity
test
Damped oscillatory magnetic
field
Power frequency immunity test
Common mode
Differential mode
Voltage dips and short
interruptionsc on DC power
supply
Voltage dips and interruptions
on AC power supply
Electromagnetic emission tests
Conducted, RF-emission
(mains terminal)
0.15...0.50 MHz
0.5...30 MHz
Radiated RF-emission,
IEC
30...230 MHz
230...1000 MHz
Type test value
100 A/m
1000A/m
100A/m, 100 kHz and 1MHz
300 V rms
150 V rms
Dips:
40%/200 ms
70%/500 ms
Interruptions:
0-50 ms: No restart
0...∞ s : Correct behaviour at
power down
Dips:
40% 10/12 cycles at 50/60 Hz
70% 25/30 cycles at 50/60 Hz
Interruptions:
0–50 ms: No restart
0...∞ s: Correct behaviour at
power down
< 79 dB(µV) quasi peak
< 66 dB(µV) average
< 73 dB(µV) quasi peak
< 60 dB(µV) average
< 40 dB(µV/m) quasi peak,
measured at 10 m distance
< 47 dB(µV/m) quasi peak,
measured at 10 m distance
1MRK 504 135-UEN A
Reference
IEC 61000–4–9, level 5
IEC 6100–4–10, level 5
IEC 60255-22-7, class A
IEC 61000-4-16
IEC 60255-11
IEC 61000-4-11
IEC 60255–11
IEC 61000–4–11
EN 55011, class A
IEC 60255-25
ANSI C63.4, FCC
Technical manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents