ABB RET650 Technical Manual page 201

Relion 650 series transformer protection
Hide thumbs Also See for RET650:
Table of Contents

Advertisement

1MRK 504 135-UEN A
Technical manual
Chosen current
phasors
Complex
power
Chosen voltage
calculation
phasors
IEC09000018 V2 EN
Figure 88:
Simplified logic diagram of the power protection function
The function will use voltage and current phasors calculated in the pre-processing
blocks. The apparent complex power is calculated according to chosen formula as
shown in table 122.
Table 122:
Complex power calculation
Mode
Set value:
L1, L2, L3
Arone
PosSeq
L1L2
L2L3
L3L1
Table continues on next page
P
Derivation of
S(angle)
S(composant)
in Char angle
Q
Formula used for complex power calculation
=
×
S
U
L
1
EQUATION1697 V1 EN
=
S
U
L L
1 2
EQUATION1698 V1 EN
= ×
S
3
U
PosSeq
EQUATION1699 V1 EN
=
S
U
L L
1 2
EQUATION1700 V1 EN
=
S
U
L L
2 3
EQUATION1701 V1 EN
=
S
U
L L
3 1
EQUATION1702 V1 EN
Section 8
Current protection
t
S(angle) <
Power1
t
S(angle) <
Power2
P = POWRE
Q = POWIM
IEC09000018-2-en.vsd
*
*
+
×
+
×
I
U
I
U
I
L
1
L
2
L
2
L
3
L
3
(Equation 57)
*
*
×
-
×
I
U
I
L
1
L L
2 3
L
3
(Equation 58)
*
×
I
PosSeq
(Equation 59)
*
*
×
-
(
I
I
)
L
1
L
2
(Equation 60)
*
*
×
-
(
I
I
)
L
2
L
3
(Equation 61)
*
*
×
-
(
I
I
)
L
3
L
1
(Equation 62)
TRIP1
START1
TRIP2
START2
*
195

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents